I. INTENT OF SPECIFICATION

A. It is the intention that this specification shall cover a complete Duplex Pump Lift Station Electrical Control System as hereinafter described and all necessary appurtenances which might normally be considered a part of the complete electrical system for this installation. All of the automatic control equipment is to be supplied by one manufacturer. It shall be factory assembled, wired and tested and covered by complete electrical drawings and instructions.

B. The control system described hereafter is a Model Powerpack Express FP4 Control System as manufactured by Siemens Water Technologies - Control Systems of St. Paul, MN. The naming of a manufacturer of equipment in this specification is not intended to eliminate competition or prohibit qualified manufacturers from offering equipment. Rather, the intent is to establish a standard of excellence for the material used, and to indicate a principle of operation desired. The contractors bid shall be based on the use of Siemens Water Technologies - Control Systems equipment. Unless the bidder clearly indicates in his bid that he is offering an equal product approved by the engineer via a pre-bid submittal, the bid shall be considered as providing the brand name product referenced in the specifications above.

C. It is important for all bidding contractors to note that if alternate proposals based on substituted systems are to bid, they must be prequalified by the consulting engineer fifteen (15) days in advance of the bid date. In the event a prequalified system is installed by the Contractor and does not meet the specified intent of this specification with regard to reliability, efficiency, functional capability, or other system parameters, the Consultant may reject the alternate system. In such instance, the Siemens Water Technologies - Control System originally specified must be furnished. The Owner or the Consultant may exercise this option at any time during the project tenure. Project tenure is defined as beginning the date the project bids and ending on the date the system has operated satisfactorily for one year after final acceptance.

D. Signal conditioning, setpoint, control, alternation, logic function, transducer, alarm and all other control functions shall be performed by solid-state modules which shall be standard catalog items of the system manufacturer, with proven field performance.

E. At least one module of each type used in the system shall be stocked by the system manufacturer for system expansions or renewal parts purposes. The modules shall be of a compatible, integrated control family with a full range of control/protective/alternation/telemetry capabilities and associated housings, enclosure system and appurtenances to perform a variety of functions required by this project and foreseeable expansion. It is the intention of this specification to disallow non-standard, "one of a kind", experimental, unproven combinations of equipment.

F. The level sensors shall be standard products manufactured and stocked by the control supplier in order to assure one source responsibility, ready availability, proper system interconnections and reliable, long-term operation.

II. SYSTEM COORDINATION AND SINGLE SOURCE RESPONSIBILITY

A. The equipment provided shall be a completely integrated automatic control and monitoring system consisting of the required automation and alarm monitoring equipment in a factory wired and tested assembly. The automatic control and alarm/monitoring system components shall be standard, catalogued, stocked products of the system supplier to assure one source responsibility, immediately available spare/replacement parts, proper system interconnections and reliable long term operation.

B. All equipment and materials shall be subject to the Engineer’s review and shall not be purchased or manufactured until the review is complete.

C. The Supplier shall prepare detailed design information, procure, configure, install, start-up, make ready for use, the complete instrumentation’s systems as indicated on the Plans and in each of these Specifications. These Specifications and drawings include descriptions of functional operation and performance, as well as standards, but do not necessarily enumerate detailed specifications for all components and devices that are essential for system operation. However, all components and devices shall be furnished and installed as required to provide complete and operable systems for accomplishing the functions and meeting the performance set forth hereinafter.

D. The system shall be installed by the Supplier complete and ready to operate, including all necessary connections to sources of electrical power, interconnection between field equipment and accessories as specified or as recommended for best operation for the equipment furnished. The hardware that is installed in the control and monitoring system shall be readily available. None of the hardware in the system shall be part of a discontinued line or classified as hardware that is on repair status only. The Supplier shall provide documentation verifying the continuing availability of the system hardware for full integration of the original hardware with future hardware improvements. All necessary mounting panels, stands, hangers, and brackets shall be furnished and installed and shall comply with the relevant sections of the Specifications.

E. The Supplier shall include in the bid allowance for factory-trained service personnel to supervise and install, adjust all the equipment until the system has been completely accepted.

III. QUALITY ASSURANCE

A. The Supplier shall maintain quality in both design and workmanship as well as materials used in manufacture of equipment supplied. All equipment supplied under this Contract shall be of new manufacture.

B. The Supplier shall be a firm that is engaged in the manufacturing of process control systems. The system shall be in regular production with pre-designed hardware and software for process control systems. When the specification conflicts with a manufacturer’s standard system, the standard system may be furnished if the intention of the specification is met.

C. System shall be a standard system. Custom one of a kind application software and customized hardware components will not be accepted. A standard system is defined as one which is available, at time of bid, with fully tested hardware and software, full documentation, and prepared training classes such that no development must be done beyond system configuration.

D. Supplier shall be responsible for detailed engineering, manufacture, programming, test, start-up and demonstration of all equipment and software programs to provide a complete operating system.

E. The Supplier shall have been continuously involved in the design and manufacture of control systems for the past ten-(10) years. The Supplier shall have successfully built and placed into operation, system similar to the one proposed herein and will furnish a list of at least ten (10) operating installations upon request by the Engineer. The Supplier shall have on staff at least ten (10) qualified instrument technicians and shall maintain a stock inventory of spare parts for all major components in the system.

F. The Supplier shall be responsible for engineering and implementing necessary interface between the supplied equipment and the existing equipment or interface junction boxes. Supplier shall document this interface including point-to-point wiring diagrams.

G. Provide all engineering and render coordination assistance, necessary for calibration of overall control system and to resolve interface discrepancies between panels, equipment, instrumentation and final control devices. Where interface conflicts exist, the Supplier shall document conflicts in writing to the City providing absolute information such as terminal numbers, device name, tests performed and diagnosis of problem.

H. All of the equipment listed herein shall be furnished by a single supplier.

I. All equipment supplied shall be of the most current and proven design at the time of delivery. The completed System and the equipment provided by the Supplier shall be compatible with the functions required and shall be a complete working System.

J. All electrical components of the System shall operate on 120 volt, single- phase, 60 Hertz current, except as otherwise noted in the specifications and on the drawings.

K. The Supplier shall be Siemens Water Technologies - Control Systems, or equal.

IV. DOCUMENTATION

A. The complete assembly shall be provided with job-specific wiring diagrams, parts lists, enclosure dimensional and door layout drawings and instructions.

B. Shop Drawings shall be submitted for approval for all equipment herein specified. The Shop Drawing Submittal shall include a Document List. An Order Specification shall be included which shall describe in detail all equipment provided. Each panel shall be provided with a job-specific wiring diagram, parts list, enclosure door layout and enclosure dimension drawing. Manufacturer's wiring diagrams that are not job-specific (standard drawings with options crossed out, etc.) are not acceptable. The wiring diagram requirement applies to all field mounted instrumentation and control equipment. Interconnection details shall be shown for all field mounted instrumentation. A Description of Operation shall be provided detailing the operation of the complete system, including the control and alarm handling.

C. Provide As-built Drawings and Instruction Manuals. These manuals shall include corrected Shop Drawings. In addition, a detailed Programming and Operations Manual for the Microprocessor-based Controller Unit shall be included. The manual shall include all information as detailed for the Shop Drawing Submittals above.

V. PRESUBMITTAL INFORMATION REQUIRED FOR ALTERNATE MANUFACTURES

A. The Engineer will issue an addendum describing acceptable equipment prior to the bid date. The bidder shall include all expenses necessitated by use of non-specified equipment in his bid price.

B. Presubmittal data shall include, but not be limited to, the following requirements to be submitted to the Engineer not less than 15 days prior to bid date:

1. Full description and performance data on all substitute items proposed with references for verification of performance for such equipment already in service, all data in triplicate.

2. Detailed description of how the proposed substitute differs from that specified including but not limited to materials of construction, fabrication, operation, warranty, service, corrosion protection, power consumption, maintenance requirements, etc.

3. Detailed discussion of why the proposed substitute is equal or superior to that specified in material of construction, fabrication, operation, warranty, service, corrosion protection, power consumption, maintenance requirements, etc.

4. Tracings and four copies of revised prints reflecting in detail any and all changes in arrangements for materials, equipment, piping, fabrication, erection, maintenance, power supply, etc.

5. Name and telephone number of person(s) to contact to answer questions or supply additional information.

C. Failure to name an approved manufacturer in each space provided in the proposal, will constitute grounds for declaring the bid irregular, or if the Owner chooses, will give the prerogative of equipment selection solely to the Owner. If more than one manufacturer is named in any space it will declare that the Bidder has no preference and will give the prerogative of equipment selection solely to the Owner.

VI GENERAL EQUIPMENT REQUIREMENTS

A. U.L. SERIALIZED LABEL

1. The control panel(s) shall be constructed in compliance with Underwriter's Laboratories Categories 698A and 913 standards – “Enclosed Industrial Control Panel Relating to Hazardous Locations with Intrinsically Safe Circuit Extensions” listing and following-up service. The control panel(s) shall bear the Underwriter's Laboratories serialized label for “Enclosed Industrial Control Panel Relating to Hazardous Locations with Intrinsically Safe Circuit Extensions”.

2. Prior to shipment from the manufacturer's facility to the jobsite for installation, an Underwriter’s Laboratories (U.L.) representative shall inspect the completed control panel(s). Upon successful completion of the inspection, the panel shall be assigned the required “Enclosed Industrial Control Panel Relating to Hazardous Locations with Intrinsically Safe Circuit Extensions” serialized U.L. label, indicating the equipment is built in accordance with the practices and requirements of the Underwriter's Laboratories 698A and 913 categories.

3. While the use of U.L. listed components is encouraged, their use alone and/or the alternate use of a U.L. 508A – “Enclosed Industrial Control Panel” serialized label will not be considered an acceptable or satisfactory alternate to the “Enclosed Industrial Control Panel Relating to Hazardous Locations with Intrinsically Safe Circuit Extensions” serialized label specified above. Upon request from the Engineer, the panel manufacturer shall supply documentation to the owner proving they are a U.L. recognized manufacturing facility for the type of equipment required. Only the labeled products of U.L.698A and 913 “Enclosed Industrial Control Panel Relating to Hazardous Locations with Intrinsically Safe Circuit Extensions” recognized panel manufacturer shall be considered acceptable for use on this project.

B. WIRING

1. All wiring shall be minimum 600 volt UL type MTW or AWM and have a current-carrying capacity of not less than 125% of the full load current. The conductors shall be in complete conformity with the national electric codes, state, local and NEMA electrical standards. For ease of servicing and maintenance, all wiring shall be color coded. The wire color code shall be clearly shown on the drawings, with each wire's color indicated.

2. All control wiring shall be contained within plastic/PVC wiring duct with covers. Where dimensional constraints prevent the use of wiring duct, wires shall be trained to panel components in groupings. The wire groupings shall be bundled and tied not less than every 3 inches with nylon self-locking cable ties as manufactured by Panduit or equal.

3. Every other cable tie shall be fastened to the enclosure door or inner device panel with a cable tie mounting plate with pressure tape. Where wiring crosses hinged areas such as when trained from the inner device panel to the enclosure door, spiral wrap shall be used.

C. INCOMING SERVICE AND LIGHTNING ARRESTOR

1. The service pole and metering will be done ahead of the lift station control panel as provided by the ______. The lift station control panel shall be service entrance rated. Conduit and wiring between the power company termination and the lift station shall be furnished and installed by the contractor. The power supply will be (240 Volt, 3 Phase, 3 wire, 60 Hertz) (208 or 240 volts, 3 phase, _____ wire, 60 Hertz) (480 volts, 3 phase, 3 wire, 60 Hertz).

2. A lightning arrestor shall be supplied in the control system and connected to each line of the load side of main power disconnect. The arrestor shall protect the control system against damage as the result of transient voltage surges caused by lightning interference, switching loads and power line interference’s. It shall begin shunting to ground at 1000 volts maximum.

3. All metering shall be done ahead of the main disconnect and control panel. The meter shall be installed by the Contractor in accordance with local power company requirements.

4. Each panel shall be supplied with a properly sized control power circuit breaker. The breaker shall supply power to all control wiring within the enclosure.

D. NAMEPLATES

1. All major components and sub-assemblies shall be identified as to function with laminated, engraved bakelite nameplates, or similar approved means.

VII CONTROL SYSTEM AND CONTROL PANEL

A. ENCLOSURE

  1. The described equipment shall be housed in a (Pick one)

(NEMA 3R Galvanized Cold Rolled Painted Steel RAL 6003 Forest Green)

(NEMA 3R Galvanized Cold Rolled Painted Steel ANSI 61 Gray)

(NEMA 3R Galvanized Cold Rolled Painted Steel Beige) )

(NEMA 3R, 304 Stainless Steel)

(NEMA 3R, 304 Stainless Steel Painted RAL 6003 Forest Green)

(NEMA 4 Cold Rolled Steel Painted Gray)

(NEMA 4X 304 Stainless Steel)

Unit shall measure 36" wide, 48" high, 12” deep. The enclosure door shall be provided with a 3 point padlock-able latch and aluminum dead front operator’s inner door.

2. This weatherproof, rain-tight enclosure shall be designed specifically for mounting in an unprotected outdoor location. It shall have a gasketed, hinged, front weather door with locking capability, and an internally mounted hinged dead front panel so that all the components normally actuated by Operating Personnel are accessible without opening the dead front and yet are not exposed to the elements or to unauthorized personnel.

Optional –

(). The enclosure shall be supplied with 18" floor stands and louvered skirts to cover incoming conduit

made out of the same material as the enclosure.

Optional –

(). Fully insulate the interior of control panel with ¾” close cell foam (½” on the inside of the outer door). Insulation must be affixed per UL 508A standards.

B. INCOMING POWER CIRCUIT INTERRUPTS

1. The control panel shall include a thermal magnetic main circuit breaker to provide an incoming power disconnect means and short circuit/overcurrent protection for the control panel equipment

2. The circuit breaker must have a minimum symmetrical RMS ampere interrupting capacity of (Pick One)

(25,000 @ 240 volt)

(65,000 @ 240 volt)

(100,000 @ 240 Volt)

(18,000 @ 480 volt)

(65,000 @ 480 volt)

The circuit breaker shall be operable through the operator’s door of the enclosure and shall have a trip rating to allow full voltage starting and continuous operation of the motors.

3. The commercial power input to the control panel/main breaker shall be UL service entrance rated and labeled.

Optional (EMERGENCY DISCONNECT (MANUAL TRANSFER SWITCH))

(). The control panel shall include a second circuit breaker mechanically interlocked with the main breaker to function as a emergency power interrupt and manual transfer switch. The breakers shall allow the control panel to be powered by either commercial power or the owners portable emergency power generator. The interlock shall be padlock-able with both breakers in the “off” position. The breakers shall be operable from the control panel operator’s door.

Optional (GENERATOR RECEPTACLE)

(). A generator receptacle with angled backbox shall be provided and mounted on the side of the enclosure by the panel manufacture. The Generator receptacle shall be of the metallic NEC style configured to UL 1686 specifications. Receptacle must be suitable for NEMA 4X environments. Cable clamps must be of contoured smooth 2-screw design. Wire terminals must be of the increased safety design. The receptacle shall be Appleton Electric.or equal, rated at (100 or 200)amperes, 600 VAC/250VDC, 50-400 Hertz .

(). The generator receptacle shall be style 1 (Grounded through receptacle collar)

() The generator receptacle shall be style 2 (Grounded through receptacle collar and plug pin)

Optional –

CONTROL POWER TRANSFORMER

Required if incoming service is 480 or 240 volt 3 wire service (Pick One)

() The control panel shall include a control power transformer for converting the high voltage incoming three phase service to 120 VAC single phase power. The 120 VAC power shall be used to power internal control components. The control power transformer shall be rated for 230/460-120 VAC single phase at 500VA with Class 105 Deg. C insulation and shall be UL Listed. The control power transformer shall be supplied with primary and secondary fusing.

Or

(). The control panel shall include a control power transformer for converting the high voltage incoming three phase service to 120 VAC single phase power. The 120 VAC power shall be used to power internal control components and the 15 amp rated GFI duplex receptacle. The control power transformer shall be rated for 230/460-120 VAC single phase at 2 KVA with Class 105 Deg. C insulation and shall be UL Listed. The control power transformer shall be supplied with primary and secondary fusing.

The control power transformer shall be of single epoxy resin impregnated construction to eliminate the possibility of moisture, dust, dirt, and industrial contaminants from affecting operation and shortening transformer life. The unit shall have integrally molded barriers between terminals and transformer to protect against electrical creepage.

C. PHASE FAILURE/UNDERVOLTAGE PUMP PROTECTION

1. A power monitor shall be provided to monitor incoming voltage and provide protection to the motors. The power monitor shall detect incoming service abnormalities including phase-loss, unbalance, reversal, over voltage, under-voltage and rapid cycling protection and provide automatic cutout of pumps and provide local alarm. Upon detection that incoming power has returned to normal, the unit will restore pump operation and discontinue alarm. The power monitor shall be protected against overcurrent by the use of separately mounted extractor-type line voltage fuses. This device shall have a nominal 2-4 second dropout delay and (2-300 second) adjustable restoration time delay.

2. The power monitor shall have built in dual color LED indicator. The indicator shall be green when system is normal and shall turn red upon detection of improper three phase power. The unit shall protect itself from voltage spikes and transients with internal transient protection meeting IEEE 587 standards.

3. The power monitor system shall also include a stagger time delay function providing time delay between lead and lag pump start to eliminate simultaneous starting of motors upon return of system power. This feature shall be operation in all modes of pump operation.

D. BRANCH CIRCUIT BREAKERS AND MOTOR STARTERS

1. A thermal magnetic circuit breaker shall be supplied as branch circuit protection for each pump motor. The circuit breaker must have the same minimum ampere interrupting capacity as the main breaker. The circuit breakers shall be operable through the operator’s door of the enclosure and shall have a trip rating to allow full voltage starting and continuous operation of the motors.

2. A NEMA rated, full-voltage, across-the-line magnetic motor starter with (ambient-compensated, quick-trip class 10 overload sensing for submersible pumps) (ambient compensated, standard trip class 20 overload sensing for standard pumps) in each phase to provide over current and running protection shall be provided for each pump motor. The overload trip setting shall be operator adjustable within normal pump operating ranges. Operator’s door mounted overload reset push-buttons shall be provided.

3. 120 VAC control power for each motor starter coil and H-O-A selector switch shall be provided.

4. A control power circuit breaker shall be provided and operable through the operators door of the control panel to provide a disconnect means and short circuit protection for any 120 VAC (or less) devices not powered from motor starter circuits.

5. Combination motor starters shall be furnished for the following motors:

Motor

HP

FLA

NEMA Starter Size

Ckt Bkr Trip

Motor 1

Motor 2

E. PUMP CONTROL SELECTOR SWITCHES AND “RUN” LIGHTS

1. The control panel shall have three position selector switches mounted on the front door for Hand-Off-Auto operation of each pump. In the Hand position the motor shall be called to operate. In the Off mode the motor shall not be allowed to operate. In the Auto mode, the motor shall operate in response to control signals from the controller.

2. Selector Switch(s) shall be industrial rated heavy duty NEMA 4 with modular contact block assemblies. Contact Blocks shall be stacking snap on type with parallel double break contacts with wiping action. Contact blocks shall be rated NEMA A600, 600 Volt, 10A continuous duty, 7200VA make, 720VA break AC. Contacts shall have compression type screw terminals with self lifting spring washers to insure that the wire remains secure even under sever vibration. Each contact block shall meet “touchsafe” requirements of IEC.

3. Unless specified otherwise, Selector Switch(s) shall be of the maintained position.

4. An operator’s door mounted, 30.5 mm diameter, NEMA Type 4X oil tight pilot light with a “Green” lens and replaceable bulb shall be provided for each pump to indicate a "pump running" condition.

Option – 5. Light shall be push to test type to permit operator testing of bulb illumination.

F. PUMP RUNNING TIME METERS

1. An operator’s door mounted, 120 VAC powered running time meter measuring hours and tenths of hours of operation up to 99999.9 hours shall be furnished for each pump motor indicated.

Optional – 2. Provide a 3rd door mounted, 120 VAC powered running time meter measuring hours and tenths of hours of operation up to 99999.9 hours shall be furnished for simultaneous pump run time.

G. CONTROLLER

1. A Pump Controller shall be furnished to automatically provide wet well level alarm monitoring and control of pumps based on float switch inputs. The controller shall be flexible for future considerations and come preconfigured with multiple modes of control for up to 2 pumps in either a pump up or pump down mode of operation as based on up float switch inputs. Operation mode shall be easily adjusted by the operator via built in rotary switch. No special tools or programming shall be required to change operation modes. This application will utilize duplex pump down mode control based on 5 float inputs representing Low Level, common pump stop, lead & Lag pump required, and high level alarm.

2. The Pump Controller shall allow easy operator selection of pump sequences via built in switch. Operator shall be able to operate pumps in a fixed pump sequence or alternating sequences. The controller shall allow operator removal of pumps from operation for service or repair via built in switch adjustments.

3. The Pump Controller shall have user adjustable built in delay timers to prevent inadvertent starting and stopping of pumps and prevention of nuisance alarms based on momentary signal input(s). Time delay shall also protect motors from operating to quickly after a power failure and allow power to stabilize before allowing motors to start. The timer should allow a minimum adjustable time delay period of 1-255 seconds allowing delay flexibility for each specific station.

4. The Pump Controller shall have built in float input sequence failure logic. The presence of this alarm shall signify a possible float switch failure, tangling or wiring problem. Upon detection of this failure, the audible alarm output shall be activated.

5. The Pump Controller shall interface to motor starter pilot circuits and alarm circuitry via built in relay outputs. Each output shall have a minimum contact rating of 7 Amps @ 240 VAC ensuring reliable and long life operation of inductive loads such as motor starters and solenoids. All outputs shall be form A with the exception of the audible alarm output, this shall have a form C contact allowing fail safe configurations. The controller shall be able to accept an external alarm acknowledge signal that will inhibit (Silence) the audible alarm output. The audible alarm output shall be activated upon detection of high, low or (Float Switch) out of sequence alarm.

6. The Pump Controller shall be able to accept a discrete input for inhibiting the operation of the pumps. Upon activation of the input, the controller will disable only the pump required outputs and will flash the associated output activation LED to indicate external inhibit. Level alarms shall still activate alarm outputs. Upon release from the inhibit signal, the pumps that are required will be allowed to restart while enforcing the start delay.

7. The Pump Controller shall be supplied with local status indication, via long life LEDs, of float input status and control and alarm output status. LEDs shall be illuminated when the associated input or output is active. LEDs shall be located on the front of the controller so they are easily viewed.

8. The Pump Controller shall operate on 120 VAC power source, be UL 913 listed for intrinsically safe operation in Class I, Divisions 1 & 2, Groups A,B,C,D operation and be certified to CE 61000-4 standards for electro-static discharge, radio frequency, and fast transient immunity.

9. Pump Controllers that require programming software to make changes and do not provide the above flexibility will not be accepted. The controller shall be a Model CB1000 as manufactured by Siemens Water Technologies.

H. FLOAT SWITCH

1. The contractor shall furnish, install, and wire the float switches for control as shown on the drawings.

(Pick One)

LS Float

2. Each float shall have molded polyethylene body, internal redundant polyurethane foam flotation, potted switch and cable connections and fine-stranded AWG #18 cable with heavy-duty synthetic rubber jacket in lengths as required to run unspliced to the control panel. The floats shall include internal weight allowing suspended operation without the use of special pipe or suspension mounting systems.

3. The float switches shall be Model LSC Floats as manufactured by Siemens Water Technologies..

9G-EF Float

2. Float switch(s) shall be designed to insure long life and reliable operation in both water and wastewater applications. Float switch body shall be constructed of Teflon coated 20 Ga. 316 stainless steel housing measuring not less than 5 ½” in diameter. A long life, high reliability, potted SPST magnetic reed switch rated for not less than 100 VA at up to 250 Volts shall be mounted inside the float and connected to a multi-stranded, 2 conductor plus ground, 16 gauge, CPE jacketed cable. The cord shall have fine strand conductors (Not more than 34 Gauge) made especially for heavy flexing service. The cable connection point shall be potted in epoxy providing a strong bond to the float and reed switch forming a water/moisture tight connection. A flexible Neoprene sleeve, not less than 1/8” thick, shall be provided over the CPE jacketed cable extending not less than 5” from the top of the mounting bracket extending down through the cable mounting bracket hinge point to the top of the float switch body, providing cable stress point relief and extended operational life.

3. A 316 SS ring flanged cable mounting clamp assembly shall be supplied allowing pipe or cable mounting as specified below. The float cable-mounting bracket shall be flared on both sides providing hinge point stress relief to both sides of the cable.

4. The float switch assembly shall provide a minimum of two pounds of buoyancy in solutions with a specific gravity of 1.0 (water) and shall have an operating temperature rating of –35 to +90 Deg. C.

5. The float switches shall be Model 9G-EF Floats as manufactured by Siemens Water Technologies..

(Option)

I. CONVENIENCE RECEPTACLE

1. An operator’s door mounted 120 VAC duplex ground fault interrupter (GFI) type, convenience receptacle rated at 15 amperes shall be supplied for the operation of a trouble light, drill, etc. It shall be protected by a separate 15 ampere trip rated circuit breaker accessible from the operator’s door.

J. LOCAL ALARM SYSTEM

1. A top mounted weatherproof, strobe alarm indication light assembly with shatter resistant polycarbonate red lens mounted on a polycarbonate/ABS blend case shall be provided. The alarm light shall be NEMA 4X rated, suitable for indoor or outdoor mounting and operate on 120 VAC and be PLC rated. The strobe tube shall provide a minimum of 300,000 peak candela output and shall be rated for 3,000 hour life.

2. The alarm light shall flash upon occurrence of an alarm condition.

Optional –

3. A left side mounted weatherproof, audible alarm horn assembly with silence push-button, shall be provided. The alarm horn suitable for indoor or outdoor mounting and operate on 120 VAC. The horn shall provide a minimum of 78dB output and shall be rated for at least 400 hour life @ 50% duty cycle. The push-button shall be 30.5mm, NEMA 4X rated. All pilot devices specified herein are to be Square D Class 9001 Type SK Line.

K. CONDENSATION PROTECTIVE HEATER

1. A 100 watt, 120 VAC condensation protective heater and adjustable high temperature cutout thermoswitch shall be supplied in the control panel. The heater’s surface area for heat dissipation shall be large enough to prevent a skin burn (if an operator’s hand should inadvertently come in contact with the unit when energized).

() (Optional) OVER-TEMPERATURE PUMP PROTECTION & PUMP SEAL FAILURE ALARM

1. Over-temperature protection shall be provided in the control panel to operate in conjunction with the over-temperature switch in each pump motor. The control shall provide pump operation lockout upon the occurrence of high temperature.

2. The circuitry shall also include a 30.5 mm diameter, NEMA Type 4X, red “pump overtemp” shutdown alarm indicating light (with front replaceable bulb) and a 30.5 mm diameter, NEMA Type 4X, manual reset push-button on the operator’s door for each pump motor.

3. An operator’s door mounted 30.5 mm diameter, NEMA Type 4X red seal fail alarm light (with front replaceable bulb) and a panel mounted seal leakage relay (to operate with the pump seal leak sensor) shall be provided to indicate a pump seal failure alarm condition for each sewage pump. The seal leakage relay shall be of solid state design incorporating LED for visual indication of sensor activation. Unit shall include built in low voltage sensor and electrical surge protection. Unit shall be CSA approved and UL recognized.

Optional-

  1. ALARM AUTODIALER

() The control panel shall include a minimum of 13” x 11” chassis space for mounting customer supplied or future alarm dialer.

Or

SENSAPHONE EXPRESS

(). A four-channel automatic telephone dialer shall be furnished to dial emergency alarm messages to up to four (4) field programmable destinations as selected by the Engineer or Owner. The dialer unit operate via plug in wall transformer.

(). The unit shall be a four-channel device utilizing normally open or normally closed dry contacts. The alarm inputs shall be connected to time delay circuitry which will inhibit dialing to insure that "nuisance" calls will not be made. If at any time the input returns to normal for more than four (4) seconds, the time delay circuitry shall be reset.

(). When the alarm input time period requirement is satisfied, the unit shall connect itself to the telephone line. The dialer shall than dial the highest priority telephone number, utilizing a touch tone or pulse dialing scheme, followed by a wait period to insure adequate time for several rings. The alarm message for the activated channel shall then be delivered via digitized voice input. The unit shall automatically hang-up after delivering the message or detection of busy signal or no answer and go on to the next highest priority number, following the same sequence previously described. This progression shall continue through to the lowest priority, then repeat itself until the call is acknowledged. The digitized voice message for each of the four (4) alarm channels shall be user configurable.

(). The following alarms shall be annunciated through the dialer:

1.

2.

3.

4.

(). The automatic telephone dialer shall include the following

features:

1. Allow keypad entry of telephone numbers.

2. Provide key pad entry of the number of rings allowed before proceeding to the next telephone

number.

3. Monitor the temperature where the unit is located within presettable limits.

4. Allow personnel to access the dialer from another site via telephone and receive a status report of

each monitored condition.

5. Provide battery backup to allow operation during a power failure for up to

twelve (12) hours.

6. Ability to call and listen to site sounds

7. Stores up to eight 32 digit phone numbers.

8. Non-Volatile memory for voice and programming storage

9. Digitally records user's voice for ID message and alarm messages. Can be recorded locally or

remotely.

(). The alarm dialer shall be a Sensaphone Express as manufactured by Phonetics, Inc.

Or

RACO CHATTERBOX MODEL CB-4

(). Description & Phone Number Dialing: The dialer shall be a solid state component capable of dialing from one to eight phone numbers, each up to 16 digits in length. Phone numbers are to be entered via the system’s keyboard. Standard pulse dialing or Touch Tone DTMF dialing shall be selected at the keyboard.

(). Additional Field Programming Capabilities: The user may optionally elect to alter the following parameters from their standard normal default values via keyboard entry. The built-in voice will guide and confirm the following programmable features.

** User Programmable Speech: Alarm and normal messages for each channel shall be programmable from a standard 230 word vocabulary.

** Remote Programming: The dialer shall permit user to change any user entered programming (except speech messages) from any touch tone phone. User shall also be able to cause a ninth phone number to be called on command to test system and phone line integrity.

** Alarm response delay: .l to 999.9 seconds.

** Delay between alarm call outs: .l to 99.9 minutes.

** Alarm reset time: Programmable 0.1 to 99 hours or “NO RESET”.

** Incoming ring response (answer) delay: 1 to 20 rings.

** Number of message repetitions: Programmable 1 - 20 repetitions of the message.

** Station ID number.

** Input alarm criteria: Each channel shall be independently configured for “Alarm On Open Circuit”, “Alarm On Closed Circuit”, or “No Alarm” - report on inquiry only, or in lieu of alarming, accumulate equipment running time.

** Autocall Test: When enabled, the unit shall place a single round of test calls, both at the time this function is enabled and also at regular subsequent intervals until this function is disabled at the keyboard. The voice shall identify these calls as test calls.

** Run Time Meter: Each channel shall be keyboard programmable to accumulate and report the number of hours that its input contacts have been closed.

(). Nonvolatile Program Memory Retention: User-entered programming shall be kept intact even when all power is removed for up to ten years.

(). Acknowledgement: Acknowledgement of an alarm phone call is to be accomplished by pressing a Touch Tone@ “9” as the alarm call is being received, and/or by returning a phone call to the unit after receiving an alarm call, at the user’s choice.

(). Synthesized Voice: The Automatic Telephone Dialer is to communicate via a highly intelligible solid state voice synthesizer (magnetic tape loops will not be used) with an identification of its location and the specific alarm conditions(s) that exist.

(). Input Monitoring Function: The unit shall continuously monitor the presence of AC power and the status of four contact closure inputs. AC power failure, or violation of the alarm criteria at any input, shall cause the unit to go into alarm status and begin dial-outs.

(). Alarm Message:Upon initiating an alarm phone call, the system is to “speak” only those channels that are currently in “alarm status”.

(). Inquiry Message and Function: Inquiry phone calls can be made directly to the unit at any time from any telephone, locally or long distance, for a complete status report of all variables being monitored, including power status. Further, by pressing the Touch Tone® "0" ,the user may hear all user-entered programming and diagnostic counts (Cumulative counts of Call In Count, Dial Out Count, Acknowledged Alarm Count, Power Off Alarm Count). All this information shall be available by keyboard inquiry at the unit as well.

(). Power Battery Backup: Normal power shall be 105-135 VAC, 15 watts maximum. The product is to contain its own gel cell rechargeable battery which is automatically kept charged when AC power is present. The battery is to be capable of keeping the product operating, and user programming intact, for a minimum of six continuous hours in the event of power failure. Shorter backup time shall not be acceptable. The built-in charger shall be precision voltage controlled, not a “trickle charger” to minimize recharge time and maximize battery life available.

(). Phone Line:The dialer is to operate on a standard rotary pulse or Touch Tone “dial-up” phone line (direct leased line not to be required) and is to be F.C.C. approved. A regular private line is to be provided. Connection to the telephone is through an industry standard 4-pin modular jack (RJ-11).

(). Integral Surge Protection: Gas tube and solid state surge protection is to be provided on all inputs, including power, phone and signal lines. These protectors are to be integrally incorporated into the main circuit board for maximum protection. Protectors mounted external to the main circuit board shall not be an acceptable substitute. The installer shall provide a good electrical ground connection point near the unit to maximize the effectiveness of the surge protection.

(). Modular Upgrades: The system shall include expansion connectors to accommodate field upgrades for analog input monitoring.

(). Additional Features: Sealed Switches, LED Indicators, Alarm Disable Warning. Talk-Through:All keyboard and front panel switches shall be sealed to prevent contamination. Front panel LED’s shall indicate: Normal Operation, Program Mode, Phone Call in Progress, Unacknowledged Alarm, Acknowledged Alarm, AC Power Present, AC Power Failure, and Low or Discharging or Recharging Battery. On any Inquiry telephone call or On-Site status check, the voice shall provide specific warning if no dialout phone numbers are entered, or if the alarm switch is in the “disable” position, or if AC power is off or has been off since last reset. A built-in microphone shall allow anyone at a remote phone to listen to local sounds and to have a two-way conversation with personnel at the dialer.

(). U.L. Listing:The dialer shall comply with U.L. 1459 and U.L. 1950.

Dialer as manufactured by RACO, Model CB-4.

VIII. FIELD SUPERVISION

1. The services of a factory trained, qualified representative shall be provided to inspect the completed installation, make all adjustments necessary to place the system in trouble-free operation and instruct the operating personnel in the proper care and operation of the equipment.

2. (It is required that the existing system be kept on line during the start up phase of the new system.( If Applicable) After each system has been installed, the Supplier shall demonstrate with simulated I/O the performance of each unit, and document that the system operates properly as specified. Monitoring signals shall register at all required locations and loop checks on all loops shall have been completed and tested. Each station must be tested and accepted by the city prior to proceeding to the next installation.

IX. TRAINING

1. The Supplier shall provide systems training for operations staff totaling no less than 4 hours.

2. All training shall be at the customers offices located in ( Location ) All travel and per-diem expense for training will be the responsibility of the Supplier.

X. GUARANTEE

1. All equipment shall be guaranteed against defects in material and workmanship for a period of one year from the date of Owner's final inspection and acceptance to the effect that any defective equipment shall be repaired or replaced without cost or obligation to the Owner.