1.01 THE REQUIREMENT
A. The Contractor shall furnish, test, install and place in satisfactory operation the pressure indicating transmitters, with all spare parts, accessories, and appurtenances as herein specified and as shown on the Drawings.
1.02 RELATED WORK SPECIFIED ELSEWHERE
A. Control and Information System Scope and General Requirements
B. Powered Instruments, General
PART 2 -- PRODUCTS
2.01 GAUGE PRESSURE INDICATING TRANSMITTERS
A. Gauge pressure transmitters shall be of the capacitance type with a process]isolated diaphragm with silicone oil fill, microprocessor]based electronics, and a rangeablility of 10:1 input range. Transmitters shall be weatherproof, submersible, and corrosion resistant construction with low]copper aluminum body and Ceramic process wetted parts. Accuracy, including nonlinearity, hysteresis and repeatability errors shall be plus or minus 0.10 percent of calibrated span, zero based. Output shall be linear isolated 4]20 milliamperes 24 VDC. Power supply shall be 24 VDC, two-wire design.. Overload capacity shall be rated at a minimum of 10 MPa. Environmental limits shall be 0-194 degrees F at 0]100% relative humidity.
B. Where scheduled, gauge pressure indicating transmitters shall be calibrated in feet of liquid for liquid level service.
C. Gauge pressure transmitters shall be Model 9700 as manufactured by Rosemount-Mobrey, or equal.
PART 3 -- EXECUTION
3.01 REQUIREMENTS
A. Refer to the Specifications.
- END OF SECTION -